Cable restraint test reports and configuration notes

Short-circuit report register

Use the complete report, including test-rig photographs, cable details, currents, duration and verdict. Reports describe the objects and arrangements tested; they are not blanket approvals of every mounting method.

Report objects and test configurations
ReportTest-object references as printedConfiguration and fixed-cleat spacingSource PDF
PDL-26.102.02LFFC-F0815M***-A900 / CFFC-F0815M***-A900Configuration 5; 300 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.102.03LFFC-F1015M***-A900 / CFFC-F1015M***-A900Configuration 7.1; 600 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.102.04LFFC-F1015M***-A900 / CFFC-F1015M***-A900Configuration 2; 300 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.102.05LFFC-F0615M***-A900 / CFFC-F0615M***-A900Configuration 12; 300 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.102.06LFFC-F0615M***-A900 / CFFC-F0615M***-A900Configuration 13; 600 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.160.04LFFC-F1015M***-A900 arrangements; CFAC-F0430M*** also appears in the test programme300 and 600 mm centres. Separate normally wrapped, double/triple cross-wrapped and bracket rigs.Download complete report
Test programme (PDF, page 4)
PDL-26.160.05LFEC-F1030M*** / CFEC-F1030M***Rigs 4 and 11; uncoated, double wrapped with rubber channel; 300 and 600 mm centres.Download complete report
Test programme (PDF, page 4)
PDL-26.160.07LFEC-F1230M*** / CFEC-F1230M***Rigs 5 and 12: uncoated, double wrapped with rubber channel at 300/600 mm. Rig 15 adds D70309 at 300 mm.Download complete report
Test programme (PDF, page 4)

How to read a cable-restraint test result

The test programmes in these eight reports describe trefoil cable formation with Class 5 cable and cite IEC 61914:2021. Their programme duration is 100 ms; the measured durations in the result tables differ. Read the recorded test values and the applicable clause for the exact configuration.

  • Object and rig: match the printed product reference to its configuration, wrap, support and photographs. A similar product code does not establish equivalence.
  • Current: summary tables list phase peak-current values. Appendix A records peak and RMS values separately. Keep the phase, units and current quantity with any quoted number.
  • Spacing and duration: fixed-cleat centres, actual test duration and cable formation are part of the result. A programme target is not a measured result.
  • Clause and verdict: keep the clause, oscillogram number and pass/fail observation together. Results under clause 9.5.2 and 9.5.3 must not be combined into a single unsupported rating.

These are summaries of existing reports, not additional product ratings. Use the complete report and the project engineer's requirements for final selection. The issuer's conclusion limits the results to the investigated test objects.

Report-specific results and limitations

The notes below identify differences that matter when choosing evidence. Refer to the complete source for all phases, specimens, observations and test-rig details.

PDL-26.102.02

The result table includes repeated tests and specimen replacements. Its 65.0 kA L1 peak row is Osc. 36 under clause 9.5.2; the clause 9.5.3 rows have different currents.

Source: test programme and result tables, PDF pages 4-6. The complete report contains the rig photographs, observations and measurement details.

PDL-26.102.03

The result table records separate clause 9.5.2 and 9.5.3 tests. Use the configuration photographs as well as the code and spacing.

Source: test programme and result tables, PDF pages 4-5. The complete report contains the rig photographs, observations and measurement details.

PDL-26.102.04

The listed result is a clause 9.5.2 test. Do not describe this report alone as evidence of a clause 9.5.3 result.

Source: test programme and result tables, PDF pages 4-5. The complete report contains the rig photographs, observations and measurement details.

PDL-26.102.05

Several current levels are recorded. The 40.2 kA L1 peak belongs to Osc. 18 under clause 9.5.2; Osc. 19 under clause 9.5.3 records 40.4 kA L1 peak.

Source: test programme and result tables, PDF pages 4-6. The complete report contains the rig photographs, observations and measurement details.

PDL-26.102.06

Separate clause 9.5.2 and 9.5.3 rows each record 35.7 kA L1 peak, with different phase values and durations.

Source: test programme and result tables, PDF pages 4-5. The complete report contains the rig photographs, observations and measurement details.

PDL-26.160.04

The LFFC result tables distinguish rigs 1, 2, 3, 8, 9, 10 and 17. The report prints D70109 for its bracket rig; B380 uses D70309. Confirm the assembly and bracket identity before applying a result.

Source: test programme and result tables, PDF pages 4-6. The complete report contains the rig photographs, observations and measurement details.

PDL-26.160.05

The 300 mm rig has a clause 9.5.2 result. The 600 mm rig has separate clause 9.5.2 and 9.5.3 results. Keep the rubber-channel arrangement and rig photographs with the result.

Source: test programme and result tables, PDF pages 4-5. The complete report contains the rig photographs, observations and measurement details.

PDL-26.160.07

The 300 mm rubber-channel rig, 600 mm rig and bracket rig have separate result rows. In the bracket rig, 118 kA and 117 kA L1 peaks refer to different clause tests; neither should replace a direct-to-rung brochure value.

Source: test programme and result tables, PDF pages 4-6. The complete report contains the rig photographs, observations and measurement details.

Source review: UES Promura website document summaries checked against the eight linked laboratory reports on 17 October 2026. This date records the website source check, not a new laboratory test or technical certification.

Configuration checks

The current B380 distinguishes cross-wrap, direct-to-rung and bracket arrangements. Historic summaries may use different examples. Do not carry a rating across arrangements simply because a part family is the same.

PDL-26.160.04 includes separate double/triple cross-wrap and bracket test rigs. PDL-26.160.07 distinguishes the uncoated arrangement with a liner from the bracket arrangement. Bracket references and complete assembly details must be confirmed before supply.

B380 page 5 lists 115 kA for its uncoated 3/4-inch direct-to-rung arrangement. The 117 kA L1 peak in PDL-26.160.07 belongs to the separate D70309 bracket rig under clause 9.5.3. These source labels must stay with their results. Any unresolved manufacturer-summary or calculator combination still requires UES Promura configuration review; this source summary does not change the calculator's selection rules.

Request configuration and report confirmation · Return to calculator